GENT XENEX FIRE ALARM PANEL – 2 ZONE CONVENTIONAL 13270-02 LB
FEATURES:-
- Number of Zones – 2
- Maximum Load Per Zone – 3mA
- Number of Sounder Circuits – 2
- Maximum Sounder Circuit Load – 0.5A per circuit (Total Load Not To Exceed 1A)
- Batteries (Not Included) – 2 x 12V 2.1Ah (See Related Products)
- Battery Standby (Using Above Specified Batteries) – 72 Hours plus 0.5 Hours Alarm Load
- Aux Relay Contacts – 1 N/O and 1 N/C Pair, 1A at 24V
- Approx Weight (With Batteries) – 5.8Kg
- Relevant Standard – EN54 Parts 2 and 4
- Approvals – LPCB Approved to EN54 Parts 2 and 4
- Cable Entry – 13 Top and 13 Rear
- Cable Type – BS 6387, 2 Core, min 1.5mm Square CSA
- Class Change Facility – Via Normally Open Push Button Switch Located No More Than 100m From Panel
- Temperature – Indoor 0 – 40 Degrees Celcius
This is the Gent Xenex 13270-02LB. This fire alarm panel complies fully with the European standard EN54 Parts 2 & 4 and can be used on installations meeting BS 5839: Part 1. Each panel contains its own integral power supply and battery support for up to two alarm sounder circuits, two auxiliary relay contacts, a zone disablement facility and a one man test and commission facility, all simplifying system design, installation and commissioning.